Generator Warning Light
1. Verify that the battery is fully charged.
2. Verify that the drive belt deflection/tension is correct. (See DRIVE BELT INSPECTION.)
3. Turn the ignition switch to ON and verify that the generator warning light illuminates.
4. Verify that the generator warning light turns off after the engine is started.
Generator
Voltage
1. Verify that the battery is fully charged.
2. Verify that the drive belt deflection/tension is correct. (See DRIVE BELT INSPECTION.)
3. Turn off all electrical loads.
4. Turn the engine switch to start the engine and verify that the generator rotates smoothly without any noise while the engine is running.
5. Measure the voltage at the terminals shown in the table.
Standard voltage
* : Turn the following electrical loads on and verify that the voltage reading increases.
- Headlights
- Blower motor
- Rear window defroster
Current
1. Verify that the battery is fully charged.
2. Verify that the drive belt deflection/tension is correct. (See DRIVE BELT INSPECTION.)
3. Disconnect the negative battery cable.
4. Connect an ammeter, capable of reading 120 A or above, between generator terminal B and the wiring harness.
5. Connect the negative battery cable.
6. Turn off all electrical loards.
7. Start the engine and increase the engine speed to 2,000-2,500 rpm.
8. Turn the following electrical loads on and verify that the current reading increases.
- If generator terminal B current will not increase, repair or replace the generator as necessary.
Note
Standard current (Reference)
Measuring conditions Room temperature: 20 °C {68 ° F} Voltage: 13.5 V
Engine hot
* : Must not be 0 A
Mazda 6 Service Manual: Electrical troubleshooting tools
Jumper wire
A jumper wire is used to create a temporary circuit. Connect the jumper
wire between the terminals of a circuit to bypass a switch.
Caution
Do not connect a jumper wire from the power source line to a body
ground. This may cause burning or other damage to wiring harnesse ...
Mazda 6 Service Manual: Service cautions
HANDLING INSUFFICIENT REFRIGERANT LEVEL
If an insufficient refrigerant level is detected at troubleshooting,
do not charge (add) the refrigerant. Because an accurate amount of
refrigerant cannot be determined from the pressure indicated on the manifold
gauge, never charge the refrigeran ...